Minimum Energy Performance Standards and Labelling for Air Conditioners with Cooling Capacity = 7.1kW

Source: International Energy Agency
Last updated: 17 October 2019

TESTING STANDARD

ISO 16358-1:2013

MS ISO 5151:2012

 

RATING AND TESTING CONDITION

CSPF for non-inverter type is calculated by multiplying EER tested at standard temperature condition by 1.062

    CSPF = 1.062 x Tested EER

 

CSPF for inverter-type, the 50% load cooling capacity test will be used with the following tolerance

    50% load = 100 % load capacity x 0.5 (tolerance ± 5.0 %), where 100% load capacity refers to measured cooling capacity during 100% load cooling capacity.

 

Testing conditions will be based on:

     - climactic ambient T1, refer to MS ISO 5151

     - Voltage 230V, 50Hz

 

STAR LABELLING (in CSPF, Wh/Wh)

The rated cooling capacity < 4.5kW

5-star: =5.30

4-star: 4.60 =CSPF<5.30

3-star: 3.30 = CSPF<4.60

2-star: 3.10 = CSPF<3.30

1-star: <3.10

 

4.5kW =Rated Cooling Capacity = 7.1kW

5-star:  = 5.10

4-star:  4.00= CSPF<5.10

3-star:  3.10= CSPF<4.00

2-star:  2.90 = CSPF<3.10

1-star:  <2.90

 

MINIMUM ENERGY PERFORMANCE STANDARDS (MEPS)

MEPS requirement is 2-stars, hence 3.10 Wh/Wh (for less than 4.5 kW) and 2.90 Wh/Wh (for less than 7.1kW)

 